Question and Answers

Q:

What are the power requirements for my dual fuel slide in range model 79041032801?

A:

Thank you for your question and I understand your concern.

You will need to see what the Kw rating is which is located on the model/serial plate on the range. The information I'm providing below is based on a 240 voltage supply.

If your model is rated between 0-16.5 Kw then it should have 40 amp service.

If the Kw rating is between 16.6 and 22.5 Kw then it should have a 50 amp service. I also added information in the image below. If you have any doubts, I recommend calling an electrician to properly connect your range to the power supply.

Read More
Joey S -
Sears Technician
May 02, 2011
Q:

Ampage on stove

A:

I provided the KW rating and electrical information that your electrician will need to install the new outlet for this range. This information is directly from a contractor specification sheet for the range.

In case you need it, here is the full installation guide for the range: Installation Instructions . It may take a minute or so for this manual to download once you click on the link. (This manual will not have the information provided below but it does have other data that may be useful.)

Let us know if you need more help.

Read More
Lyle W -
Sears Technician
April 23, 2011
A:

The image that I provided above indicates that the range requires a minimum breaker size of 25 amps. That may be the information that they are seeking. If you need more help, let me know.

Read More
Lyle W -
Sears Technician
May 02, 2011
See more answers