Question and Answers

Q:

On a refrigerator compressor, which is the common, start and run prong?

A:

Typically, the common terminal is on top by itself. The run terminal is usually on the right and the start terminal is on the left. To check this, (with the refrigerator unplugged) you could take resistance readings on the terminals. From the common to the start terminal, you should measure between 3 to 11 ohms. From the common to run terminal, you should measure between 1 and 5 ohms. Between the start and run terminals, you should get the sum of the above resistance readings (start plus run winding resistance).

Read More
Lyle W -
Sears Technician