Q:

Heat pump recycling every 5 seconds on my Frederick PDH15K5SD-C thru the wall A/C -Heatpump

A:

It can be very aggravating when your A/C continuously recycles and displays error codes. While you are waiting for your expert answer, I did some research on the unit. At this time, I was unable to locate information that would be helpful in regards to your question. Some of these questions that are asked will need specific research and will be answered by an expert with-in two business days but usually sooner.

Read More
Julio -
November 01, 2012
A:

Thank you for using Manage My Life. Your PTAC unit is flashing error code 02 because there is inadequate power being supplied to the unit. The unit requires a minimum of 200VAC for 230VAC units and 240VAC for 265VAC units. The minimum is just that, the minimum. Low voltage input will lead to premature failures and if this has been ongoing, the unit may not even operate if the minimum requirement is met. It may require closer to 220VAC or 250VAC.

Read More
Andrew D -
Sears Technician
November 01, 2012
A:

You may want to call an electrician and have them check the voltage in your power panel, that uses a double pole breaker, the feeder breaker to your A/C may be bad, or there may be a loose connection at the local disconnect, some have fuses inside and a fuse my be blown, if all that is ok then your power company isn't suppling the correct voltage to your residence.

Read More
John -
November 01, 2012
A:

I meant to say the A/C unit uses a double pole breaker, that is its feeder breaker, have the electrician check all connections for tightness

Read More
John -
November 01, 2012